400KVA变压器铝合金电缆三相短路电流计算表
变压器电阻 变压器电抗 母线单位电阻 母线单位电抗 母线电阻 母线电抗 电缆单位电阻 电缆单位电抗 电缆长度 电缆电阻 电缆电抗 总电阻 总电抗值 三相短路电流值 Rt Xt Rm' Xm' Rm Xm Rl' Xl' Rl Xl 3.83 15.54 0.057 0.148 0.456 1.184 2.276 0.08 22.76 0.8 27.046 17.524 7.137 3.83 15.54 0.057 0.148 0.456 1.184 2.276 0.08 34.14 1.2 38.426 17.924 5.424 3.83 15.54 0.057 0.148 0.456 1.184 2.276 0.08 45.52 1.6 49.806 18.324 4.334 3.83 15.54 0.057 0.148 0.456 1.184 2.276 0.08 56.9 61.18
500KVA变压器70mm2双拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 3.0112.440.0430.130.3441.040.1610.071101.610.714.96414.1915.299 3.0112.440.0430.130.3441.040.1610.071152.4151.0655.76914.54514.699 3.0112.440.0430.130.3441.040.1610.071203.221.426.57414.914.123 3.0112.440.0430.130.3441.040.1610.
2000KVA变压器70mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.564.770.0090.0520.0720.4160.520.074105.20.745.8325.92627.663 0.564.770.0090.0520.0720.4160.520.074157.81.118.4326.29621.856 0.564.770.0090.0520.0720.4160.520.0742010.41.4811.0326.66617.844 0.564.770.0090.0520.0720.4160.520.074
1250KVA变压器300mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.977.620.010.0580.080.4640.1220.07101.220.72.278.78425.351 0.977.620.010.0580.080.4640.1220.07151.831.052.889.13424.015 0.977.620.010.0580.080.4640.1220.07202.441.43.499.48422.759 0.977.620.010.0580.080.4640.1220.07253.051.7
2500KVA变压器150mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.433.820.0060.0350.0480.280.2430.071102.430.712.9084.8140.920 0.433.820.0060.0350.0480.280.2430.071153.6451.0654.1235.16534.802 0.433.820.0060.0350.0480.280.2430.071204.861.425.3385.5229.952 0.433.820.0060.0350.0480.280.2430.07
2500KVA变压器50mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.433.820.0060.0350.0480.280.7290.075107.290.757.7684.8525.115 0.433.820.0060.0350.0480.280.7290.0751510.9351.12511.4135.22518.324 0.433.820.0060.0350.0480.280.7290.0752014.581.515.0585.614.316 0.433.820.0060.0350.0480.280.7290.
2500KVA变压器300mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.433.820.0060.0350.0480.280.1220.07101.220.71.6984.845.173 0.433.820.0060.0350.0480.280.1220.07151.831.052.3085.1540.755 0.433.820.0060.0350.0480.280.1220.07202.441.42.9185.536.941 0.433.820.0060.0350.0480.280.1220.07253.051
630KVA变压器120mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 2.269.920.0320.130.2561.040.3040.071103.040.715.55611.6717.795 2.269.920.0320.130.2561.040.3040.071154.561.0657.07612.02516.485 2.269.920.0320.130.2561.040.3040.071206.081.428.59612.3815.260 2.269.920.0320.130.2561.040.3040.071
2000KVA变压器25mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.564.770.0090.0520.0720.4161.4570.0811014.570.8115.2025.99614.074 0.564.770.0090.0520.0720.4161.4570.0811521.8551.21522.4876.4019.837 0.564.770.0090.0520.0720.4161.4570.0812029.141.6229.7726.8067.531 0.564.770.0090.0520.0720.416
1600KVA变压器16mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.715.960.0090.0520.0720.4162.2760.081022.760.823.5427.1769.345 0.715.960.0090.0520.0720.4162.2760.081534.141.234.9227.5766.436 0.715.960.0090.0520.0720.4162.2760.082045.521.646.3027.9764.895 0.715.960.0090.0520.0720.4162.2760.0
630KVA变压器70mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 2.269.920.0320.130.2561.040.520.074105.20.747.71611.716.411 2.269.920.0320.130.2561.040.520.074157.81.1110.31612.0714.486 2.269.920.0320.130.2561.040.520.0742010.41.4812.91612.4412.826 2.269.920.0320.130.2561.040.520.07425131
1250KVA变压器70mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.977.620.010.0580.080.4640.520.074105.20.746.258.82421.270 0.977.620.010.0580.080.4640.520.074157.81.118.859.19418.023 0.977.620.010.0580.080.4640.520.0742010.41.4811.459.56415.417 0.977.620.010.0580.080.4640.520.07425131.85
1250KVA变压器16mm2铝合金电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.977.620.010.0580.080.4642.2760.081022.760.823.818.8849.050 0.977.620.010.0580.080.4642.2760.081534.141.235.199.2846.320 0.977.620.010.0580.080.4642.2760.082045.521.646.579.6844.835 0.977.620.010.0580.080.4642.2760.082556.92
2000VA变压器下铝合金电缆短路电流计算表合
2000kva电缆截面162535507095120150185240300 电缆长度三相短路电流 10ik9.52514.07418.32623.23427.66331.04733.11334.61935.63836.64537.274 15ik6.5069.83713.18417.45521.85625.69528.30430.36631.85633.35334.306 20ik4.9317.53110.22813.84217.84421.63724.42226.77328.57030.43131.649 25ik3.9676.0928.33511.42314.99318.56421.33523.79425.76627.87129.289 30ik3.3185
1600VA变压器下铝合金电缆短路电流计算表合
1600kva电缆截面162535507095120150185240300 电缆长度三相短路电流 10ik9.34513.56917.31421.36124.74127.15928.56829.56330.22030.87031.277 15ik6.4369.63312.74216.53220.19623.18725.10926.56427.57828.58429.218 20ik4.8957.4269.99413.32316.83019.96622.14623.90025.18726.49027.325 25ik3.9466.0308.19411.10014.33017.40519.67221.59323.06724.59725.600 30ik3.3045.
基于FLN的电力系统三相短路电流计算
本文提出了一种电力系统三相短路电流计算的新方法─—人工神经网络方法。该方法使用了自适应模型识别概念和基于广义逆学习算法(gi)的函数链网络(fln)技术。fln用来估计短路电流基本特征。数值计算实例表明所提出的方法是可行的。
2000KVA变压器120mm2三拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.564.770.0250.1170.20.9360.0610.068100.610.681.376.38635.215 0.564.770.0250.1170.20.9360.0610.068150.9151.021.6756.72633.182 0.564.770.0250.1170.20.9360.0610.068201.221.361.987.06631.343 0.564.770.0250.1170.20.9360.0610.06825
2500KVA变压器300mm2双拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.433.820.0160.0780.1280.6240.0360.068100.360.680.9185.12444.183 0.433.820.0160.0780.1280.6240.0360.068150.541.021.0985.46441.269 0.433.820.0160.0780.1280.6240.0360.068200.721.361.2785.80438.701 0.433.820.0160.0780.1280.6240.036
1250KVA变压器150mm2三拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.977.620.0260.1230.2080.9840.050.067100.50.671.6789.27424.404 0.977.620.0260.1230.2080.9840.050.067150.751.0051.9289.60923.468 0.977.620.0260.1230.2080.9840.050.0672011.342.1789.94422.594 0.977.620.0260.1230.2080.9840.050.0672
2500KVA变压器240mm2双拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.433.820.0160.0780.1280.6240.0450.069100.450.691.0085.13443.960 0.433.820.0160.0780.1280.6240.0450.069150.6751.0351.2335.47940.954 0.433.820.0160.0780.1280.6240.0450.069200.91.381.4585.82438.310 0.433.820.0160.0780.1280.6240.045
1600KVA变压器70mm2双拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.715.960.0250.1170.20.9360.1610.071101.610.712.527.60628.705 0.715.960.0250.1170.20.9360.1610.071152.4151.0653.3257.96126.659 0.715.960.0250.1170.20.9360.1610.071203.221.424.138.31624.771 0.715.960.0250.1170.20.9360.1610.07125
1250KVA变压器70mm2双拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 0.977.620.0260.1230.2080.9840.1610.071101.610.712.7889.31423.657 0.977.620.0260.1230.2080.9840.1610.071152.4151.0653.5939.66922.298 0.977.620.0260.1230.2080.9840.1610.071203.221.424.39810.02421.012 0.977.620.0260.1230.2080.9840.1
315KVA变压器185mm2双拼XLPE电缆三相短路电流计算表
变压器电阻变压器电抗母线单位电阻母线单位电抗母线电阻母线电抗电缆单位电阻电缆单位电抗电缆长度电缆电阻电缆电抗总电阻总电抗值三相短路电流值 rtxtrm'xm'rmxmrl'xl'lrlxlrxik 5.3519.580.0820.160.6561.280.060.069100.60.696.60621.5510.204 5.3519.580.0820.160.6561.280.060.069150.91.0356.90621.89510.018 5.3519.580.0820.160.6561.280.060.069201.21.387.20622.249.838 5.3519.580.0820.160.6561.280.060.069251
小水电三相短路电流计算的两种方法
介绍了小型水电站相对于大型电站来说,规模小,投资省,近十几年来,各地都得到大发展。三相短路电流计算在小水电设计、施工、维护和运行过程中占有重要地位,对工程质量、电气安全至关重要,掌握简便快捷的方法,较准确地计算三相短路电流对工作有益。
某海上天然气平台空压机配电柜三相短路电流计算与分析
针对某海上天然气平台上空压机出现配电柜三相短路故障,导致配电柜内导线及插头烧毁事件,进行短路电流计算及故障分析,并对空压机配电柜进行了整改.